Florida · Fire code

The fire code in force in Florida now.

Florida Fire Prevention Code, 8th Edition (2023). Enforced by State Fire Marshal adopts; your local fire official enforces. Checked on the primary source; the state record was last reviewed 2026-11-12.

Explore Florida by location and topic

Fire code in Florida

Checked on the source
In force

Florida Fire Prevention Code, 8th Edition (2023)

NFPA 1 and NFPA 101 (2021 editions) with Florida amendments, effective December 31, 2023 per the State Fire Marshal page. The Notice of Proposed Rule for 69A-60 (approved by agency head April 30, 2026; hearing July 14, 2026) lists a proposed effective date of December 31, 2026 for the 2024 NFPA editions; final adoption not yet posted.

Source: primary document

Who enforces it

State Fire Marshal adopts; your local fire official enforces

Statewide layer. County and city amendments sit on top; confirm the local office for the address.

What changes next

9th Edition target Dec 31, 2026

9th Edition: flrules 69A-60.002 history (read Oct 21, 2026) ends with the Proposed notice of June 12, 2026 (FAR 52/114); rule still effective 12/31/2023; SFM page lists the July 14, 2026 hearing and no adoption; proposed effective date Dec 31, 2026

The federal layer

No federal fire code applies to a private building; OSHA's exit-route, fire-extinguisher and emergency-plan rules (29 CFR 1910 Subparts E and L) apply to every employer alongside the state fire code.

Dated items

Next 24 months
Dec 31, 2026
Florida Fire Prevention Code, 9th EditionState Fire Marshal · proposed effective date in the 69A-60 Notice of Proposed Rule
Confirmed date

What a building has to do

25 recurring duties

These apply when the building has the equipment or fits the type named. The frequency is the standard one; your local official can set a stricter one, so confirm it for the address.

Annual
Fire alarm system: annual inspection and testNFPA 72, Ch. 14 · Licensed alarm contractor; report to the fire marshal on request · Not yet checked line by line against the source.
Monthly
Sprinkler control valves: inspected monthly when locked or electrically supervised (weekly when only sealed); open, accessible, tamper switch workingNFPA 25, Ch. 13 · Owner or contractor; log kept · Not yet checked line by line against the source.
Quarterly
Sprinkler system: quarterly inspection (gauges, waterflow and supervisory alarm devices, fire department connection)NFPA 25, Ch. 5 and 13 · Owner or contractor · Not yet checked line by line against the source.
Twice a year
Waterflow switches (vane or pressure type) and valve tamper switches: semiannual test, signal confirmed at the panel and the monitoring company (mechanical water motor gongs: quarterly)NFPA 25, Ch. 5 and 13; NFPA 72, Ch. 14 · Licensed sprinkler or alarm contractor · Not yet checked line by line against the source.
Annual
Sprinkler system: annual inspection and main drain testNFPA 25, Ch. 5 and 13 · Licensed sprinkler contractor · Not yet checked line by line against the source.
Every 5 years
Sprinkler piping: internal inspection and obstruction checkNFPA 25, Ch. 14 · Licensed sprinkler contractor · Not yet checked line by line against the source.
Weekly or Monthly
Fire pump: no-flow (churn) test. Diesel: weekly, 30 minutes. Electric: monthly, 10 minutes, but weekly when the pump serves a building beyond the fire department’s pumping capacity, has a limited-service controller, is a vertical turbine, or draws from a ground-level tankNFPA 25, Ch. 8 · Owner or contractor; readings logged · Not yet checked line by line against the source.
Annual
Fire pump: annual flow testNFPA 25, Ch. 8 · Licensed contractor · Not yet checked line by line against the source.
Annual
Standpipes: annual inspection of hose connections, valves, caps and gaskets, piping and signageNFPA 25, Ch. 6 · Owner or licensed contractor · Not yet checked line by line against the source.
Every 5 years
Standpipes: five-year flow test (manual and dry systems also get a five-year hydrostatic test)NFPA 25, Ch. 6 · Licensed contractor · Not yet checked line by line against the source.
Monthly or Quarterly or Twice a year or Annual
Kitchen exhaust (hood, duct, fan): inspected for grease buildup and cleaned when buildup is found. Interval by cooking volume: solid fuel monthly; high volume (24-hour, charbroiling, wok) quarterly; moderate semiannually; low annuallyNFPA 96, Table 12.4 (11.4 in older editions) · Qualified exhaust cleaning company · Not yet checked line by line against the source.
Twice a year
Kitchen hood fire-suppression system: inspection and service every six months, tag datedNFPA 17A; NFPA 96, Ch. 11 · Licensed suppression contractor · Not yet checked line by line against the source.
Weekly
Generator: weekly inspection (fuel, oil and coolant levels, battery and charger, block heater, alarms, transfer switch in automatic)NFPA 110, Ch. 8 · Owner; log kept · Not yet checked line by line against the source.
Monthly
Generator: monthly exercise under load for at least 30 minutes (diesel: at least 30% of nameplate kW or the manufacturer’s minimum exhaust temperature); transfer switches operated monthlyNFPA 110, 8.4.2 · Owner; log kept · Not yet checked line by line against the source.
Annual
Generator: annual supplemental load test when the monthly runs do not reach 30% of nameplate: 50% for 30 minutes, then 75% for 60 minutes (1.5 hours)NFPA 110, 8.4.2 · Contractor with a load bank · Not yet checked line by line against the source.
Every 3 years
Generator, Level 1 (life-safety) systems: run for 4 continuous hours, or the system’s class duration if shorter, at least once every 36 monthsNFPA 110, 8.4.9 · Owner or contractor; report kept · Not yet checked line by line against the source.
Monthly
Emergency lighting and exit signs: monthly 30-second testNFPA 101, 7.9.3 · Owner; written record · Not yet checked line by line against the source.
Annual
Emergency lighting: annual 90-minute testNFPA 101, 7.9.3 · Owner or contractor · Not yet checked line by line against the source.
Monthly
Fire extinguishers: monthly visual check, initialedNFPA 10, 7.2 · Owner · Not yet checked line by line against the source.
Annual
Fire extinguishers: annual maintenance and tagNFPA 10, 7.3 · Licensed extinguisher contractor · Not yet checked line by line against the source.
Annual
Fire doors and shutters: annual inspection and testNFPA 80, 5.2 · Qualified person; written record · Not yet checked line by line against the source.
Every 4 years
Fire and smoke dampers: operational testNFPA 80, 19.4; NFPA 105 · Qualified contractor · Not yet checked line by line against the source.
Twice a year or Annual
Smoke control system: operated through each control sequence — semiannually for a dedicated system, annually for a nondedicated system that shares the building’s HVACNFPA 92, Ch. 8; IFC Sec. 909 (periodic testing) · Qualified contractor; written record · Not yet checked line by line against the source.
Monthly
Fire drills: monthly while in session, documentedFor education. NFPA 101, 14.7.2 and 15.7.2 · Owner; documented · Not yet checked line by line against the source.
Annual
Occupant load posted; crowd managers for events over 250 peopleFor assembly, retail. NFPA 101, 12.7.6 and 13.7.6 · Owner · Not yet checked line by line against the source.

Local layer by county

14 counties
Miami-Dade County
  • Miami-Dade Fire Rescue, Fire Prevention Bureau, for unincorporated areas and contract cities. Cities with their own fire department, such as Miami Beach and Coral Gables, enforce the same code through their own AHJ.
Broward County
  • Broward Sheriff's Office Fire Rescue covers unincorporated Broward and contract cities including Cooper City, Weston, and Dania Beach; larger cities such as Fort Lauderdale, Hollywood, and Pembroke Pines run independent fire-rescue departments.
Palm Beach County
  • Palm Beach County Fire Rescue is the fire marshal for unincorporated areas and most contract cities; Boca Raton, Boynton Beach, Palm Beach, Briny Breezes, Golf, Hypoluxo, and Ocean Ridge run their own fire departments.
Orange County
  • Orange County Fire Rescue's Office of the Fire Marshal enforces the Florida Fire Prevention Code and inspects existing commercial and multifamily occupancies in unincorporated Orange County.
  • Orlando, Winter Park, Apopka, Ocoee, Winter Garden, and Maitland each run their own municipal fire department and fire marshal rather than using the county's.
Monroe County
  • The Monroe County Fire Marshal's Office enforces the Florida Fire Prevention Code in unincorporated Monroe County, described by the county as running from Ocean Reef to Stock Island (office: 7280 Overseas Highway, Marathon).
  • The county lists Marathon Fire Rescue, Islamorada Fire Rescue and Key West Fire Department under 'Municipal Fire Marshals'; the page does not say each city runs its own fire code enforcement, so confirm with the city.
  • The county Fire Marshal's Office says it finds issues through annual Fire and Life Safety inspections, permit inspections and complaint investigations; the page gives no inspection fee schedule.
  • Fire plan review is done by the Fire Marshal's Office on plans submitted through the Monroe County Building Department, against the current Florida Fire Prevention Code and NFPA.
Pinellas County
  • Pinellas County has no county fire marshal named on its Fire Administration page; each of 18 municipal and independent special-district fire departments handles its own fire code inspections and prevention.
  • Ten municipal agencies and one independent district contract to serve unincorporated areas; East Lake, Palm Harbor, Lealman and Pinellas Suncoast are independent districts with their own taxing authority.
Lee County
  • Lee County's emergency services page shows fire protection by Cape Coral and Fort Myers city departments, two airport departments, and independent fire districts such as Bonita Springs, Estero, Iona-McGregor, Lehigh Acres, North Fort Myers and San Carlos Park; no county fire marshal is named.
  • For permit-related fire inspections, the county generates the inspection ticket (automated line 239-533-8997) but the local fire district performs the inspection and the county accepts sign-off only from the districts.
Collier County
  • Collier fire inspections are run by independent fire districts; for example North Collier Fire Control and Rescue District has a Fire Prevention Bureau (6495 Taylor Road, Naples) and a separate Plan Review Office.
Osceola County
  • The Osceola County Fire Rescue Office of the Fire Marshal (1 Courthouse Square, Suite 1400, Kissimmee) enforces adopted fire codes at new and existing commercial properties; the page does not say whether incorporated cities are covered.
  • Osceola's fire permits page says the currently adopted Florida Fire Prevention Code and NFPA editions apply, and publishes guidance on fire watch posting, ERCES, light-frame truss buildings and fire department access permits.
  • Osceola's Fire Prevention Fee Schedule (Appendix K, effective October 1, 2025, Resolution 25-036R) sets annual inspection fees by floor area: $50 up to 2,000 sq ft, $75, $125, $400 for 100,001-500,000 sq ft, and $600 above 500,000.
  • Under the same schedule, re-inspection fees are $105 (first), $105 (second), $210 (third) and $315 for subsequent failures; authority cited is F.S. 633.208(2), 633.216 and F.A.C. 69A-60.
Duval County
  • Jacksonville is a consolidated city-county; the Jacksonville Fire and Rescue Department Fire Prevention Division and its Fire Marshal's Office inspect commercial properties and places of assembly under state laws adopted by the City (myjfrd.com Fire Prevention page).
  • Jacksonville enforces the 2023 Florida Fire Prevention Code, 8th Edition (City Building Inspection Division codes page).
  • Fire inspection fees are posted in the City Fees schedule: Sec. 420.104 routine inspection at $0.009 per sq ft capped at $5,000, first re-inspection no charge, second re-inspection at the routine rate (jacksonville.gov/fees, read Oct 2026; confirm against current Ordinance Code).
  • Plan review fees are set in Ordinance Code Sec. 123.102 and start at $150 for buildings up to 10,000 sq ft (City Fees schedule).
Volusia County
  • Volusia County Fire Rescue serves the unincorporated county plus Pierson, Oak Hill and Lake Helen (volusia.org Fire Services page).
  • The County Fire Marshal's office enforces the Florida Fire Prevention Code, with separate fire inspection and plans review staff; the page cites no ordinance or fee schedule.
Brevard County
  • Brevard County Fire Rescue's Office of Fire Prevention performs fire and life safety inspections, plan review and fire investigation; inspectors are state-certified through the State Fire Marshal's Office (brevardfl.gov Fire Prevention page).
  • The county page says commercial fire inspections in county jurisdiction occur on a tri-annual basis; the page does not define the interval, so confirm with the office at (321) 637-5660.
  • Fire Safety Inspectors review commercial plans against Florida statutes, the Florida Fire Prevention Code and local ordinances; fee amounts are in a Fee Schedule PDF linked from the New Construction and Permitting page.
  • The Office of Fire Prevention also handles plan review and inspections for the City of West Melbourne and the Town of Palm Shores.
Polk County
  • Polk County Fire Rescue is headquartered at 1295 Brice Blvd, Bartow; its pages list Services and Permits but no fire marshal inspection program could be read.
Sarasota County
  • The Sarasota County Fire Department's Office of the Fire Marshal, 6062 Porter Way, reviews fire plans and inspects; its Fire Prevention Handbook (version 07-01-2025) states the Florida Fire Prevention Code, 8th Edition applies.
  • County job specifications for Fire Safety Inspectors say they inspect existing commercial and multi-family occupancies under State and County fire laws; no inspection interval or fee is stated there.

Questions about the fire code in Florida

Which fire code applies in Florida today?

Florida Fire Prevention Code, 8th Edition (2023). NFPA 1 and NFPA 101 (2021 editions) with Florida amendments, effective December 31, 2023 per the State Fire Marshal page. The Notice of Proposed Rule for 69A-60 (approved by agency head April 30, 2026; hearing July 14, 2026) lists a proposed effective date of December 31, 2026 for the 2024 NFPA editions; final adoption not yet posted.

Who enforces the fire code in Florida?

State Fire Marshal adopts; your local fire official enforces.

What changes next for the fire code in Florida?

9th Edition target Dec 31, 2026. 9th Edition: flrules 69A-60.002 history (read Oct 21, 2026) ends with the Proposed notice of June 12, 2026 (FAR 52/114); rule still effective 12/31/2023; SFM page lists the July 14, 2026 hearing and no adoption; proposed effective date Dec 31, 2026

Other areas in Florida

Everything in force in Florida

Free reference. No account is needed. Membership — Coming soon.