Chapter 554, F.S. and Rule 69A-51. Enforced by State Fire Marshal (Department of Financial Services), not DBPR. Checked on the primary source; the state record was last reviewed 2026-11-12.
Certificate inspections: power and high-pressure water boilers yearly, low-pressure steam every two years, hot-water heating biennial with internal every four years (s. 554.108(3), 2026 Florida Statutes). Fuel-fired boiler rooms in public lodging establishments need carbon monoxide detectors, s. 554.108(6).
Source: primary document
Statewide layer. County and city amendments sit on top; confirm the local office for the address.
In force, nothing scheduled
There is no federal boiler certificate; the state program below is the whole obligation, with the ASME Boiler and Pressure Vessel Code and the National Board Inspection Code as the referenced standards.
These apply when the building has the equipment or fits the type named. The frequency is the standard one; your local official can set a stricter one, so confirm it for the address.
Chapter 554, F.S. and Rule 69A-51. Certificate inspections: power and high-pressure water boilers yearly, low-pressure steam every two years, hot-water heating biennial with internal every four years (s. 554.108(3), 2026 Florida Statutes). Fuel-fired boiler rooms in public lodging establishments need carbon monoxide detectors, s. 554.108(6).
State Fire Marshal (Department of Financial Services), not DBPR.
Nothing is scheduled. The rule above stays in force until the state adopts a newer edition or amends the program; AHJ Radar re-checks the source weekly.