Working space around electrical equipment
A reading of NFPA 70 110.26 as it is commonly cited on an inspection report. The reading explains the section; it does not certify a building or close a citation. The inspector's finding and the code text govern.
MatchExact section: the decoder holds a reading for NFPA 70 110.26.
Evidence reviewReading prepared from the published text, NFPA 70 2023 edition; readings dated Oct 14, 2026; line-by-line source check pending. Text: NFPA free access (nfpa.org).
AdoptionWhether this standard is in force depends on the state or city that adopts it, and on the edition adopted. The decoder reads it against any of the 51 state records.
What it coversPanels and switchgear that may be worked on while energized need a clear working space in front: at least 3 feet deep (more where the equipment faces other live parts), 30 inches wide or the width of the equipment, and headroom of 6.5 feet. The space must not be used for storage.
What usually closes itClear and mark the floor in front of the panel; relocate storage; hold the dedicated space free of pipes and ducts.
Who can do the workLicensed electrical contractor
Proof at re-inspectionPhotos of the clear, marked space.
Questions to ask next: which edition and section the finding is written against, in writing; what exactly was observed and what the inspector expects at re-inspection; the correction deadline on the notice. Disagree with the reading of the code? Ask the inspector for the section and edition in writing, then the fire or building official for a written interpretation.