NFPA 101 · 7.9 · Fire protection

Emergency lighting

A reading of NFPA 101 7.9 as it is commonly cited on an inspection report. The reading explains the section; it does not certify a building or close a citation. The inspector's finding and the code text govern.

MatchExact section: the decoder holds a reading for NFPA 101 7.9.
Evidence reviewReading prepared from the published text, NFPA 101 2024 edition; readings dated Oct 14, 2026; line-by-line source check pending. Text: NFPA free access (nfpa.org).
AdoptionWhether this standard is in force depends on the state or city that adopts it, and on the edition adopted. The decoder reads it against any of the 51 state records.
What it coversEmergency lighting must run 90 minutes on loss of power; a 30-second functional test every 30 days and a 90-minute test every year, recorded.
What usually closes itReplace failed units or batteries; keep the monthly log; do the annual 90-minute test.
Who can do the workOwner staff; no license required for this task
Proof at re-inspectionMonthly and annual test log.
Read NFPA 101 7.9 against your stateGet the free weekly digest

Questions to ask next: which edition and section the finding is written against, in writing; what exactly was observed and what the inspector expects at re-inspection; the correction deadline on the notice. Disagree with the reading of the code? Ask the inspector for the section and edition in writing, then the fire or building official for a written interpretation.