Oklahoma · Boilers

The boiler inspection rules in force in Oklahoma now.

ASME BPVC, National Board Inspection Code (latest edition and current addenda), API 510 and CSD-1 (OAC 380:25-3-4). Enforced by Oklahoma Department of Labor, Boiler & Pressure Vessel program (40 O.S. Sec. 141.1 et seq.). Checked on the primary source; the state record was last reviewed 2026-11-12.

Explore Oklahoma by location and topic

Boilers in Oklahoma

Checked on the source
In force

ASME BPVC, National Board Inspection Code (latest edition and current addenda), API 510 and CSD-1 (OAC 380:25-3-4)

OAC 380:25-3-2: power boilers annual certificate inspection, internal where construction permits, plus annual external. Low-pressure steam: internal every 2 years. Hot water heating/supply boilers: annual external. Pressure vessels subject to corrosion: internal triennially, others every 10 years. Statute allows two-month grace. CSD-1 applies to boilers installed since July 1, 1995.

Source: primary document

Who enforces it

Oklahoma Department of Labor, Boiler & Pressure Vessel program (40 O.S. Sec. 141.1 et seq.)

Statewide layer. County and city amendments sit on top; confirm the local office for the address.

What changes next

In force

In force; no pending change found - rule already auto-tracks the latest ASME/NBIC edition

The federal layer

There is no federal boiler certificate; the state program below is the whole obligation, with the ASME Boiler and Pressure Vessel Code and the National Board Inspection Code as the referenced standards.

What a building has to do

1 recurring duties

These apply when the building has the equipment or fits the type named. The frequency is the standard one; your local official can set a stricter one, so confirm it for the address.

Annual
Boiler: certificate inspection per state programState boiler law · State boiler inspection program · Not yet checked line by line against the source.

Questions about the boiler inspection rules in Oklahoma

Which boiler inspection rules apply in Oklahoma today?

ASME BPVC, National Board Inspection Code (latest edition and current addenda), API 510 and CSD-1 (OAC 380:25-3-4). OAC 380:25-3-2: power boilers annual certificate inspection, internal where construction permits, plus annual external. Low-pressure steam: internal every 2 years. Hot water heating/supply boilers: annual external. Pressure vessels subject to corrosion: internal triennially, others every 10 years. Statute allows two-month grace. CSD-1 applies to boilers installed since July 1, 1995.

Who enforces the boiler inspection rules in Oklahoma?

Oklahoma Department of Labor, Boiler & Pressure Vessel program (40 O.S. Sec. 141.1 et seq.).

What changes next for the boiler inspection rules in Oklahoma?

Nothing is scheduled. The rule above stays in force until the state adopts a newer edition or amends the program; AHJ Radar re-checks the source weekly.

Other areas in Oklahoma

Everything in force in Oklahoma

Free reference. No account is needed. Membership — Coming soon.